Heating Rate Controller · Electrical Reference R1.2

Terminal distribution

Terminal block selection, conductor assignments and mounting · reference arrangement

Block selection and capacity

Each PTFIX distributor is one electrical potential with six or twelve independently accessible conductor positions. Separate distributors are required for L, N, 24 V, 0 V and each switched circuit. The protective-earth group uses a dedicated WAGO 2002-1407 ground terminal.

11Distribution groups
48Allocated terminations
70Available positions
22Unassigned positions

Download block purchase list (CSV) Download all 48 terminal assignments (CSV)

ReferenceCircuit / purposeManufacturer and selected partQtyUsed / totalSpare
X1-LMains live LPhoenix PTFIX 6X2,5 NS35 BN · 327301014 / 62
X1-NMains neutral NPhoenix PTFIX 6X2,5 NS35 BU · 327300214 / 62
X1-PEProtective earthWAGO 2002-1407 PE14 / 40
X2-24Common +24 VPhoenix PTFIX 6X2,5 NS35 RD · 327300413 / 63
X2-0VCommon 0 VPhoenix PTFIX 12X2,5 NS35 GY · 327302219 / 123
X3-24GCH1 gated +24 VPhoenix PTFIX 6X2,5 NS35 RD · 327300414 / 62
X3-EN1CH1 enabled +24 VPhoenix PTFIX 6X2,5 NS35 OG · 327301815 / 61
X3-DRV1CH1 switched drive returnPhoenix PTFIX 6X2,5 NS35 VT · 327301613 / 63
X4-24GCH2 gated +24 VPhoenix PTFIX 6X2,5 NS35 RD · 327300414 / 62
X4-EN2CH2 enabled +24 VPhoenix PTFIX 6X2,5 NS35 OG · 327301815 / 61
X4-DRV2CH2 switched drive returnPhoenix PTFIX 6X2,5 NS35 VT · 327301613 / 63

Purchase summary: Phoenix Contact PTFIX 6X2,5-NS35: brown ×1, blue ×1, red ×3, orange ×2, violet ×2; PTFIX 12X2,5-NS35 gray ×1; WAGO 2002-1407 PE ×1. This is the quantity for one complete two-channel reference assembly; distributor packaging and minimum-order quantities may be greater.

The current terminal allocation covers the listed 24 V controls, mains and PE circuits. External heater DC runs through its own rated breakers, contacts, SSRs and panel connectors; do not route a 15 A heater feed through these control-distribution groups.

DIN-rail mounting and conductor insertion

Mounting selection

The selected PTFIX …-NS35 variants are supplied ready for 35 mm top-hat DIN rail, NS 35/7.5 or NS 35/15. No separate PTFIX-to-DIN adapter is required for the selected ready-to-mount part numbers.

The WAGO 2002-1407 ground terminal is also specified for 35 × 7.5 or 35 × 15 DIN rail. Verify the rail, PE contact, mounting stability and bonding of the complete assembly.

Use the lengthwise -NS35A family only if the bill of materials and physical layout are revised to match; mounting orientations are not interchangeable part numbers.

Wiring practice

PTFIX 2.5 family: push-in termination, nominal cross-section 2.5 mm², rigid/flexible conductor range per selected manufacturer data. Phoenix specifies 8–10 mm stripping length; ferruled flexible wires must match the manufacturer's permitted ferrule and conductor range.

Use one conductor per marked port. Keep the mains, protective earth and low-voltage circuits separated and properly enclosed. Leave safe room around each connector for insertion, withdrawal, wire bend radius and inspection.

No conductive bridging between separate distribution groups. Do not use PTFIX current ratings to justify the external 15 A heater circuit or reduce protective-device requirements.

Manufacturer references: Phoenix Contact PTFIX catalogue · PTFIX 12-way technical data · WAGO 2002-1407 technical data.

Terminal allocation · 48 connections

Each port has one assigned conductor. The same reference codes are used on the electrical drawings and on the From–Via–To sheets. The remaining positions are unassigned.

X1-L Mains live L

PortConductor / endpoint
L.1J1 switched/fused L
L.2PS1 C1 (L)
L.3S1-A:13
L.4S2-A:13

4 occupied / 6 positions · 2 spare

X1-N Mains neutral N

PortConductor / endpoint
N.1J1 switched N
N.2PS1 C2 (N)
N.3E1:12 (N)
N.4E2:12 (N)

4 occupied / 6 positions · 2 spare

X1-PE Protective earth

PortConductor / endpoint
PE.1J1 PE
PE.2PS1 C3 (PE)
PE.3cabinet chassis bonding
PE.4flexible door bonding

4 occupied / 4 positions · 0 spare

X2-24 Common +24 V

PortConductor / endpoint
24.1PS1 +Vo
24.2S1-B:23
24.3S2-B:23

3 occupied / 6 positions · 3 spare

X2-0V Common 0 V

PortConductor / endpoint
0V.1PS1 −Vo
0V.2K1 N/−
0V.3SK3:A2
0V.4SB1 LED−
0V.5W1:14(−)
0V.6K2 N/−
0V.7SK4:A2
0V.8SB2 LED−
0V.9W2:14(−)

9 occupied / 12 positions · 3 spare

X3-24G CH1 gated +24 V

PortConductor / endpoint
1S1-B:24
2K1 L/+
3K1:11
4SB1:C

4 occupied / 6 positions · 2 spare

X3-EN1 CH1 enabled +24 V

PortConductor / endpoint
1K1:14
2SK3:A1
3SB1 LED+
4SSR1 A1/+3
5HL1+

5 occupied / 6 positions · 1 spare

X3-DRV1 CH1 switched drive return

PortConductor / endpoint
1W1:13(+)
2SSR1 A2/−4
3HL1−

3 occupied / 6 positions · 3 spare

X4-24G CH2 gated +24 V

PortConductor / endpoint
1S2-B:24
2K2 L/+
3K2:11
4SB2:C

4 occupied / 6 positions · 2 spare

X4-EN2 CH2 enabled +24 V

PortConductor / endpoint
1K2:14
2SK4:A1
3SB2 LED+
4SSR2 A1/+3
5HL2+

5 occupied / 6 positions · 1 spare

X4-DRV2 CH2 switched drive return

PortConductor / endpoint
1W2:13(+)
2SSR2 A2/−4
3HL2−

3 occupied / 6 positions · 3 spare

ACTIVE indicator path: Finder K1 terminal 14 → X3-EN1 → HL1 positive; Finder K2 terminal 14 → X4-EN2 → HL2 positive. The LED negative returns via X3-DRV1/X4-DRV2 and its Weidmüller demand interface. The enable distribution nets are not permanent +24 V.

DC input voltmeters · PV1 and PV2

Each Murata DMR20-10-DCM-R-C meter measures its channel's external DC supply input at TB1. The meter has an internal self-resetting fuse. The manufacturer also requires external 0.25 A / 300 V time-delay protection of supply wiring connected to TB1 (+) and TB1 (−). The exact DC-rated fuse/holder topology, placements and count require documented competent engineering selection.

Confirmed as fitted: neither PV1 nor PV2 has external meter input fuses. The two meter branches are omitted from the 48-terminal PTFIX allocations and the 70-route table; neither record is a complete as-built voltmeter connection reference. PV-FUSE-01 corrective action and inspection record →

Murata meter installation datasheet → · Equipment risk assessment →

Assembly materials

MaterialSpecification / selectionApplication
DIN rail35 mm top-hat, 7.5 or 15 mm height, securely mountedPTFIX-NS35, WAGO PE terminal and other rail components
Terminal/distributor markingsDurable group and port identification consistent with X1–X4 schedulesIdentifies circuits, positions and conductor destinations
Conductor and ferrulesCorrect insulation/temperature/current ratings, compatible size and strip lengthSecure push-in conductor termination; ferrules where specified
Segregation and cable managementInsulation barriers, ducting, cable supports, suitable clearancesSeparates mains, PE, 24 V controls and independent external DC leads
PE rail and enclosure bondingCorrect PE terminal and verified protective conductor continuityJ1, PS1, cabinet chassis and flexible door bond
Meter input wiringMurata installation specification: external 0.25 A / 300 V time-delay supply-wire fusingRequired protection, not installed in the reported configuration
External heater DC protectionSuitable source protection, 15 A duty verification, DC-rated switching and connectorsNot a PTFIX control-distribution circuit

The named PTFIX …-NS35 variants already include their mounting arrangement; do not add separate PTFIX-NS35 adapters to the purchase list unless using plain blocks. Allow for any rail end-stops and accessories required by the final rail layout and manufacturer's installation requirements.

Inspection and commissioning checks

These checks apply to installation and maintenance. This reference schedule does not constitute evidence of a completed independent electrical inspection.

As-built differences record

Record approved differences between the terminal allocation reference and the physical enclosure after inspection. Keep this record separate from the electrical connection schedule.

#Reference / terminalSpecified arrangementInstalled arrangementReviewed by / date
01    
02    
03    
04    
05    
06    
07    
08    

You can type into the blank cells before printing. Entries are not saved automatically.

Blank as-built record (CSV)