Heating Rate Controller · Electrical reference · R1.2

Connection sheets — From → Via → To

Current R1.2 connection reference. Every listed distribution-port connection and direct wire route has a unique row. Check the physical installation against the documentation before servicing; the notation legend explains the terminal symbols.

How connector references correspond

Panel ↔ R1.2 schedule

The front panel uses JP1–JP4 for the four input/output pairs, while the current route schedule uses JP1-IN/OUT for channel 1 and JP2-IN/OUT for channel 2.

ChannelPanel pairSchedule referencePurpose
1JP1JP1-INUpper PSU input
1JP2JP1-OUTLower heater output
2JP3JP2-INUpper PSU input
2JP4JP2-OUTLower heater output

Important: These are document aliases, not an independently verified physical wiring inspection. Check the permanent markings and isolate external DC supplies before making or changing connections. The engineering review includes outstanding technical checks.

Reading the wiring schedule

R1.2 · 70 numbered control and heater routes

Each row names a wire source (FROM), intermediate terminal (VIA) and destination (TO). A value in square brackets, such as [X3-EN1 common net], identifies an electrically common distribution potential, not an extra wire.

DesignationComponent typeWhere to find details
J1, PS1, E1/E2Mains inlet, control power supply and Omron controllersComponent models and datasheets
S1/S2, SB1/SB2, K1–K4CONTROL selectors, ENABLE buttons and Finder relaysComponent models and datasheets
W1/W2, SSR1/SSR2, HL1/HL2Demand interfaces, Crydom SSRs and ACTIVE indicatorsComponent models and datasheets
X1–X4Distribution terminalsTerminal-by-terminal allocation
JP, QF, PV, JTCPanel DC sockets, protection, voltmeters and thermocouple socketsComponent models and datasheets

The positive input supply to each ACTIVE LED is Finder terminal 14 via X3-EN1 or X4-EN2; the LED negative is switched through the corresponding Weidmüller interface.

Scope and protection hold point · PV-FUSE-01: these 70 numbered routes cover the documented heater and control circuits but omit PV1/PV2 voltmeter supply wiring. Manufacturer-specified external 0.25 A / 300 V time-delay protection for TB1 (+/−) input wiring is not installed on either channel. The 70 routes are not a complete as-built circuit schedule. Meter protection requirements and acceptance record →

Find a wire or terminal

70 connections shown

Printed sheets always include every connection, regardless of the on-screen filter.