13 October 2026 — portable desktop Studio redesign and Controller Explorer

  • Single-controller desktop UX: no fixed two-channel workflow. One physical E5CC-T over one selected COM port per session; free-text controller ID retained for optional audit traceability. Native shell now has an updated Segoe UI interface, purpose-first tabs, status footer and distinctive read-only/lab states.
  • FULL offline website creator bundled: offline_creator.py packages the actual website Programme Studio, including eight memories, charts, creator JSON and five-button simulator, as a standalone local HTML file launched in the default browser. This is not a second independently maintained implementation. No cable or network required. Native editor remains for file import/export and later guarded COM transfers.
  • NEW Controller Explorer: backup_explorer.py interprets a saved e5cct-backup-1 JSON in read-only mode, even without serial connection. Browse each of the eight slots; plain-English descriptions of ramp, soak and zero-rate instant SP, repetition/link; nine C3 values explained; editable assumed start PV and estimated commanded-SP chart; export text report; optional copy of a fully decoded, non-chained profile to the local editor, never to the Omron. Unknown/unsupported values prevent copying; original raw words remain in the backup.
  • Scale caution: valid Type K C3:0000=5 uses different display scaling than =6. Decoder reports candidate engineering units but physical DA values and segment types must be cross-checked against the keypad on the real COM7 unit before trusting a converted editable copy or approving any upload. PID/alarm/time-signal configurations are not fully decoded by Explorer and may limit safe replacement decisions.
  • Backup UX: progress 0/8 to 8/8, reopen and compare JSON on disk, explicit completion message, stays on Backup instead of automatically advancing to lab write tab.
  • CI regression: 27 Python backend tests PASS, Windows PyInstaller onefile successfully packaged with bundled offline website HTML, portable ZIP assembled and artifact uploaded in GitHub Actions run 38416108536, artifact name E5CC-T-Programme-Studio-Windows. No live hardware transfer run.
  • Write safety: real COM7 reports C3 0000=5 and 00BF=0; current provisional app preflight still expects 6 and 1, therefore physical uploads remain blocked. Need real controller DA programme 1 read-back / backup file and engineering verification of scaling, zero-rate step mapping and SP/PV Start semantics before supervised isolated RAM-stage test.

13 October 2026 — first eight-programme backup attempt and UI fix

  • Live operator observation: In the existing portable Windows read-only build, operator clicked READ AND SAVE ALL PROGRAMME MEMORY while connected on COM7. A timestamped JSON appeared in the selected folder and the app silently jumped from Tab 3 to Tab 4. The original success callback contained self.backupdetail.set(...); self.book.select(self.t_upload); this navigation indicates TransferSession.backup() returned without throwing, but the original build did not independently reopen or verify the saved file. The actual JSON has not been supplied for inspection; do not call this a verified backup yet.
  • Fixed in source: transfer.py now emits 1–8 block progress, verifies each group contains 150 DA registers, clears any previous backup eligibility before a new attempt, reopens the final JSON and compares its exact contents with the captured 8 × 150 registers plus nine selected C3 values before enabling a successful in-session backup flag.
  • Fixed in Windows app: app.py shows a progress bar, explicit 8/8 status with the saved path and a Backup complete — file checked dialog; remains on Tab 3, never auto-enters the Lab transfer tab; failure remains prominent and fail-closed.
  • Tests: New tests cover block progress, on-disk content equality, lack of writes, and simulated incomplete block response leaving no valid backup flag; GitHub Windows action 38412666477 passed its Test protocol and model step (21 tests). Build artifact confirmation remains separate.
  • Unrelated open issue: Current preflight still hard-codes in-t=6 and PV Start=1. Real controller has valid in-t=5 and SP Start=0; upload remains blocked deliberately until the application specification and write assumptions are reviewed. No actual write performed.

13 October 2026 — FIRST REAL COM7 READ-ONLY SERIAL CONNECTION (PASS)

  • Physical serial link PASS: E58-CIFQ2 installed with Windows virtual COM driver, Programme Studio START_READ_ONLY.cmd connected using COM7. Identity command 0503 returned model prefix E5CC-TQX3A (10 chars; model suffix still requires physical nameplate); raw status command 0601 returned 0100.
  • Configuration C3 reads PASSED: 0000=5, 0004=0, 00B9=0, 00BA=1, 00BB=0, 00BC=0, 00BD=1, 00BE=0, 00BF=0. All were actually returned by real serial I/O, unlike prior simulations.
  • Two application PRE-FLIGHT assumptions discovered to be too restrictive (not physical faults):
    1. Omron H185 §4-3 lists in-t=5 as a valid factory-default Type K, −200..1300 °C range, resolution 1 °C; in-t=6 is also Type K but narrower −20.0..500.0 °C, resolution 0.1 °C. App presently hard-codes C3:0000=6; needs a deliberate sensor-range policy and range-aware model validation before enabling any writes, not a forced setting change on the controller.
    2. Omron H186 §3-3 maps C3:00BF=0 to SP Start, =1 to PV Start. H185 §5-15-12 specifically advises rate-of-rise programming + RESET Stop Control when starting segment zero’s ramp from the measured PV; do not enable PV Start simply to get that behavior. The app presently hard-codes C3:00BF=1 in transfer.py, and README.md/builder references require that value. Correct the specification and tests before enabling writes.
  • Do NOT change hardware settings just to silence the preflight. Old app reports 7/9 match and upload blocked; this is appropriate while write assumptions are under review. Maintain USB-only setup power and leave physical heater AC/DC supplies isolated.
  • NEXT: Read-only Back up memory tab → save all eight programme blocks (DA 150 registers per programme, including previously edited Programme 1); save timestamped JSON, no overwrite, preserve copy. This is programme memory backup + nine C3 values not a complete controller configuration clone. Upload/stage/save have NOT been exercised on physical hardware.
  • Independent sources: Omron H185 https://files.omron.eu/downloads/latest/manual/en/h185_e5_c-t_users_manual_en.pdf ; H186 https://files.omron.eu/downloads/latest/manual/en/h186_e5_c-t_digital_temperature_controllers_communications_manual_en.pdf?v=1 .

E5CC-TQX3A5M-000 — front-panel simulator validation

Test type: Read-only menu inspection (not heating programme execution)
Reference: Omron H185, E5_C-T User’s Manual, §§ 3-3, 3-4, 4-1 and 4-7
Simulator: https://techtinker.club/heater/program-tools/#simulator
Target model: E5CC-TQX3A5M-000 on both channels
Issue: E58-CIFQ2 detected in Device Manager but COM-port driver unavailable (Code 28). This test does not require a COM port.

Safety boundary: Use USB setup power only, normal controller supply safely isolated, and external heater supply safely isolated. No RUN command; no MODE+DOWN RUN/RESET combination; no changes to stored parameter values or initial configuration. The only adjustable value in this test is the navigation selector d.seg (0, 1, end). Don’t change d.prg if you are uncertain what it selects. If a menu behaves unexpectedly, record it and stop rather than guessing.

S.ERR usually means a sensor input error (e.g. missing or unsuitable thermocouple). This is a separate issue from the absent Windows driver. Do not attempt to suppress it by altering in-t during the menu test.

Record these details

  • Date/time: __________
  • Physical channel: ☐ CH1 ☐ CH2
  • Full nameplate suffix (photo): __________
  • Initial upper display: ____ Lower display: ____
  • S.ERR flashing? ☐ Yes ☐ No
  • Normal mains and heater DC safely isolated? ☐ Verified
  • Controller powered by E58-CIFQ2 only? ☐ Yes
  • Menu protection message or locked key? __________

A. Basic navigation (3 minutes)

Start at normal PV/SV screen.

Check Key press Expected screen Observed screen / value
A1 Brief LEVEL once (left rectangular key) d.prg _______
A2 Brief MODE once (second looping-arrow key) s-no _______
A3 Brief MODE once d.seg with end normally _______

Do not change s-no or d.prg. Their displayed values may differ from our simulator’s default. Record them exactly.

B. Segment 0 (5 minutes)

At d.seg, select 0 using UP or DOWN. Selection is navigational; it is not the segment’s end setting. Press MODE to see the first parameter. Keep pressing MODE just long enough to record the relevant screen codes and values.

Check Omron display Meaning Actual value / visible?
B1 d.seg = 0 Selected segment _______
B2 styp Ramp / soak / step if rate-of-rise mode _______
B3 sp Target setpoint _______
B4 pr Rate slope if ramp _______
B5 time Time if applicable _______
B6 Next parameter after last segment item Menu transitions _______

Write N/A, not a guessed value, if a parameter does not appear.

C. Segment 1 (5 minutes)

Return to d.seg using MODE (brief = next; held ≥1 s = previous where supported). Select 1; press MODE and record all segment items. Do not edit them.

Check Omron display Actual value / visible?
C1 d.seg = 1 _______
C2 styp _______
C3 sp _______
C4 pr _______
C5 time _______
C6 How to return to d.seg _______

D. Initial settings — inspect, don’t edit (7 minutes)

From Programme Setting Level return to Operation by pressing LEVEL briefly three times. From Operation hold LEVEL for at least 3 seconds to display in-t. Use MODE to move through parameters, without UP or DOWN.

Screen Meaning Actual value Shown / hidden
in-t Sensor type ____ ____
d-u °C / °F ____ ____
cntl PID / ON-OFF ____ ____
t-u Programme time unit ____ ____
t-pr Programming method (critical): time or pr ____ ____
pru Rate denominator (minute/hour) ____ ____
rtsm RESET behaviour ____ ____
p-on Power-restoration behaviour ____ ____
eset Programme-end behaviour ____ ____

Important: The simulator assumes t-pr=pr, t-u=h-m and pru=m. If the real controller is in time mode, the actual segment menus differ from the simulator’s rate-mode menus. Record the mismatch; don’t change t-pr to make this test pass.

Exit the Initial Setting Level with LEVEL held at least 1 second.

E. Safe navigation checks (2 minutes, optional)

  • From a parameter page, hold MODE ≥1 s: did the display return to the previous parameter? ____
  • Brief LEVEL presses correctly cycle Operation → Program → Adjustment → PID → Operation? ____
  • d.seg=end behaves as programme-wide settings, not an END segment? ____

Do not test RUN/RESET, output controls, editable digit shifting or protected/advanced settings during this session. PF can be user-configured to another function, so leave it alone for now.

Physical controller observation — 13 October 2026 (Channel not yet identified)

Reported by user while controller is powered from E58-CIFQ2 with Windows driver unavailable (Code 28). Normal sensor input currently reports flashing S.ERR.

  • Before change: t-pr=time; when d.seg=0, the actual controller displayed only sp and time. This is consistent with step-time programming and does not prove the simulator’s rate-of-rise display is wrong.
  • User-initiated change: t-pr was changed to pr; the resulting Segment 0 parameters were subsequently observed (see below).
  • Observed configuration: pru=m, t-u=h-m, rtsm=stop, eset=rst. Originally p-on=cont; user subsequently changed p-on=rst. Confirmed retained after full USB unplug/reconnect power cycle on 13 October 2026; actual RUN-to-power-loss recovery and physical output behaviour remain untested.
  • Programme-wide end settings: With d.seg=end, physical controller showed rpt=0 (no repeat) and link=end (no chaining). Together with eset=rst, the configured programme is intended to enter RESET after finishing, subject to bench verification.
  • Programme slot: d.prg=0 physically observed; all segment and end-menu values above relate to currently selected programme 0.
  • PID selection and programme alarm display values: pid=1, al-1=0, al-2=0, al-3=0 physically observed under d.seg=end for programme 0. These are displayed alarm setpoints, not evidence that alarms are disabled: actual alarm types, output assignments and function are unverified. The PID gain/time values were not measured or modified.
  • After switching to t-pr=pr: The user confirmed s-no=1 (one active segment: segment 0). Setting d.seg=0 revealed styp=ramp → sp=50 → pr=0 in that order. Validates the rate-mode display flow. Omron H185 §4-7-4 explicitly says pr=0 causes the segment to behave as a step despite styp=ramp; a positive rate must be set for an actual ramp. Do not run the test profile yet.

  • Safety follow-up required: Omron H185 §4-7-4 explains that p-on=cont restores interrupted controller programme status. For the heater cabinet, recommend assessment of p-on=rst to inhibit automatic post-power-loss continuation. This concerns loss of Omron controller supply, not ordinary PWM/SSR switching of the independent heater DC supply. rtsm=stop alone is not physical isolation; Omron H185 §6-5 confirms mv-r (MV at Reset) is an Adjustment Level parameter masked by default, with factory default 0.0% for standard control. Its actual value is not yet verified on this unit. Do not change parameter masking merely to display it; verify later by a qualified commissioning method alongside the hardware fail-safe.
  • Navigation result confirmed: With d.seg=0, styp=ramp → sp=50 → pr=0, one further short MODE displayed d.seg=end, rather than pid. This is consistent with re-entering programme-wide parameter selection. Updated simulator MODE navigation to match the observed single-segment flow (commit 65da4e0e96d04f2f1c119b3134b776d459849482). Three alarm screens (al-1, al-2, al-3) were also observed between pid and rpt; the real controller displayed 0 for each on programme 0. The simulator now shows 0 for these three on slot 0 only (commit 1bba13726904372237201c806d46429b6f75367f), not implying actual alarm disablement or verified values on other programmes. Multi-segment return behaviour remains to be tested.
  • Menu loop physically confirmed: With programme 0 selected and d.seg=end, pressing MODE after link=end returns to d.prg=0, exactly as the simulator currently does. This completes the read-only single-segment Programme Setting Level navigation comparison (including displayed pid=1, al-1=al-2=al-3=0, rpt=0, link=end).
  • LEVEL transition confirmed: Starting from d.prg=0 in Programme Setting Level, one brief LEVEL press displayed l.adj (Adjustment Level). The user did not report the lower-display value, so no value is assumed.
  • SP mode confirmed: User reports spmd=psp (Program SP Mode) on the physical Omron. This is an Adjustment Level parameter. Exact key (MODE vs LEVEL) used to move from l.adj to spmd has not been confirmed; do not infer it.
  • PID-level transition confirmed: From spmd=psp in Adjustment Level, user pressed brief LEVEL and observed d.pid=1 (reported as dpid). This confirms the PID Setting Level entry and selection of PID set 1. Actual PID tuning values are not recorded; earlier movement from l.adj to spmd was probably MODE, but user was unsure.
  • PID proportional band observed: A brief MODE from d.pid=1 showed 1.p (user transcribed i.p) with lower display reported as 8. This is PID set 1 proportional band; Omron H177 E5_C-T programming diagram lists factory default 8.0 (temperature units °C). Exact displayed decimal place not confirmed by user, so retain reported value 8 in field notes.
  • PID integral time confirmed: From 1.p, brief MODE displayed 1.i=233 (user replied ‘yep’ to expected code/value), corresponding to PID set 1 integral time, 233 seconds. No parameter edits performed.
  • PID derivative time confirmed: From 1.i=233, brief MODE displayed 1.d=40, PID set 1 derivative time 40 seconds. No edits reported. PID set 1 recorded as P=8 (reported display, decimal unverified), I=233 s, D=40 s.
  • PID output upper limit confirmed: From 1.d=40, brief MODE displayed 1.olh=100, corresponding to PID set 1 manipulated-variable (MV) upper limit of 100% as defined by Omron H185 §5-10. This is a control-output percentage limit, not an electrical current limit or physical safe isolation setting. No change made.
  • PID output lower limit confirmed: From 1.olh=100, brief MODE displayed 1.oll=0, corresponding to PID set 1 MV lower limit of 0%. P=8 (displayed as reported), I=233 seconds, D=40 seconds, OLH=100%, OLL=0%. None of this establishes safety of physical output at RESET; these are PID set bounds, not independent hardware isolation.
  • PID automatic selection upper limit confirmed: From 1.oll=0, brief MODE displayed 1.aut=1320. Omron’s official E5_C/E5_C-T H177 datasheet identifies 1.aut as PID 1 Automatic Selection Range Upper Limit with illustrated default 1320. This is not an autotune command. Actual automatic PID-selection behaviour is not tested.
  • Thermocouple input test — basic functional pass: User connected a Type K thermocouple while controller was USB setup-powered; the flashing S.ERR disappeared and the displayed temperature looked sensible. User subsequently confirmed that gently warming the thermocouple junction caused the displayed temperature to rise and then fall after release. This validates qualitative response direction and continuity, not calibrated accuracy, output behaviour or any heater controls. No mains or heater supply was required. Windows USB driver remains missing (Code 28).
  • Main LEVEL loop physically confirmed: From d.pid=1 in PID Setting Level, one brief LEVEL press returned to the normal Operation Level display, where S.ERR was flashing. Together with previous observations, the short-LEVEL sequence Operation → Programme (d.prg) → Adjustment (l.adj) → PID (d.pid) → Operation has been confirmed. S.ERR is a sensor-input error to be checked separately, not evidence of a menu/USB driver fault.
  • PID menu loop physically confirmed: From 1.aut=1320, one brief MODE returned to d.pid=1. The real unit, in its current configuration, does not show 1.lba between them. Physical sequence: d.pid=1 → 1.p=8 → 1.i=233 → 1.d=40 → 1.olh=100 → 1.oll=0 → 1.aut=1320 → d.pid=1. This is a display/menu validation, not verification of PID performance. The simulator was updated to match this observed set-1 read-only navigation, commit eb1f352ba9ad03d7341f96b81076ba3edbb64ac0, and its button sequence checked with a mock DOM.
  • Next validation: Continue checking other read-only menus (e.g. Operation Level), or plan an isolated multi-segment programme navigation test once deliberate programming is approved. Keep heater supply isolated and do not RUN. Other PID sets, PID editing behaviour and physically masked settings are not yet validated.
  • Limitations: USB-only inspection provides no heater-output or restart-interlock qualification.

Two-segment manual-entry test — 13 October 2026 (in progress)

  • User deliberately changed s-no from 1 to 2 while the actual selected slot was d.prg=0 (confirmed by user afterward). Thus the modification was applied to Programme 0, not Programme 1. This was identified before editing segment content. Instructed user to restore Programme 0 s-no=1 first, then select d.prg=1 and inspect its existing s-no. Reversion and programme switch not yet confirmed.
  • Programme 1 pre-edit observation: User reports s-no=8 after being instructed to select d.prg=1. This is eight active segments, not proof the programme is empty. No existing segment data has yet been backed up. s-no=8 recorded before intentional test changes. Programme 0 restoration to s-no=1 was requested but not explicitly re-confirmed.
  • Next action: With external heater supply disconnected, confirm permission to repurpose Programme 1 before reducing s-no to 2; original eight active segments and any stored values would no longer all be active. Then inspect selected segments before changing setpoints, times and rates. No RUN.
  • Intended isolated, non-running test profile: Segment 0 ramp to 50 °C at 2 °C/min, Segment 1 soak 15 min (0.15 with t-u=h-m), rpt=0, link=end, eset=rst. No external heater supply.
  • Segment 0 entered: User reports having configured Segment 0 sp=50, pr=2 in Programme 1 (the chosen ramp-and-soak test). Exact styp setting at this time not independently re-read; previously instructed to set it to ramp.
  • Physical multi-segment navigation confirmed: With s-no=2 and d.seg=0, pressing MODE immediately after pr=2 automatically displayed d.seg=1. This differs from the single-segment case where the same key press displayed d.seg=end. Simulator updated to auto-select next active segment and to show end after the last segment (commit a760438bd970f2e52a6c6c887c20492355f3bebb). Both the one-segment and two-segment cases passed mocked-button sequence checks; more-than-two progression is extrapolated, not hardware-verified.
  • Final-segment menu navigation confirmed: In the two-segment Programme 1 test, user reports MODE advanced from the last Segment 1 parameter to d.seg=end, then another MODE advanced to pid=1. This validates final-segment return to programme-wide settings. Segment 1 values physically confirmed by user: styp=soak and time=0.15 (15 minutes with t-u=h-m). Segment 0 had been entered as styp=ramp (not re-read), sp=50, pr=2. Programme 1 rpt, link and full-profile run behaviour remain unverified.
  • Programme 1 ending confirmed: User read rpt=0 and link=end under d.seg=end for Programme 1. Combined with controller-wide eset=rst, this is the intended finish-without-repeat/chain configuration, but the actual RUN/end behaviour and outputs have not been tested.
  • USB power-cycle retention test — both segments pass: After unplugging E58-CIFQ2 until controller powered down and reconnecting, user confirmed Programme 1 s-no=2, Segment 0 styp=ramp, sp=50, pr=2, and Segment 1 styp=soak, time=0.15 all persisted. Programme 1 completion settings (rpt, link) have not yet been re-read after this power cycle. No RUN or output activation.
  • Programme-wide completion settings retained after power cycle: On Programme 1 after the same USB power cycle, user confirmed rpt=0 and link=end still displayed under d.seg=end. Full manually entered profile confirmed to persist: d.prg=1, s-no=2, segment 0 styp=ramp, sp=50, pr=2, segment 1 styp=soak, time=0.15, rpt=0, link=end. Controller-wide eset=rst had been observed before power cycle; its persistence was not rechecked in this specific sequence.
  • Test outcome: PASS for manual button entry, menu progression, and configuration readback after full USB power removal and restoration. NOT YET TESTED: programme execution/RUN sequence, measured PV tracking, timing against actual heater, control SSR output, RESET output behaviour, any safety interlock or USB communications.
  • Next action: With normal mains and heater DC safely isolated and controller USB powered, navigate to normal Operation Level and inspect displayed status/read-only RESET indication without pressing RUN or changing any parameter. Record screen codes, actual PV, and displayed state. Bench commissioning and controlled heater testing require separate safety review.

Operation Level follow-up — 13 October 2026

  • Physical navigation: After returning from PID Setting Level to Operation Level and connecting the Type K sensor, user pressed MODE once. Real controller displayed a-m (Auto/Manual Switch). This corrects the previous simulator assumption that first MODE would display r-r.
  • Next Operation Level screen physically confirmed: One brief MODE after a-m showed pgsg=0.00. Omron H185 §6-3 defines pgsg as Programme Number / Segment Number Monitor, formatted programme.segment (e.g. 2.03 means programme 2, segment 3). Here monitor reports programme 0, segment 0; this must not be mistaken for the previously edited Programme 1. During RESET, the monitor does not imply active heating.
  • Crucial difference: In H185 §6-3, d.prg (Programme Setting Level) chooses the editing target, while prg (Operation Level) chooses which programme is used at RUN when RESET and no event-input programme override. prg on this particular controller has not yet been read, and should be checked before any RUN test. Never assume d.prg=1 means Programme 1 will run.
  • Simulator patch: Added pgsg and prg at their documented operation-menu positions and separated edit programme from RUN programme in the virtual model. Stub later operation monitors are approximations of H185 and not physical-hardware verified. Virtual selection of prg is allowed only in RESET. Commit fa5a518424ec37ddc6dcb2ce2ab8be88249cae4b; mock-button tests passed.
  • Safety: Omron H185 §§5-11/6-3 states holding LEVEL for at least three seconds on a-m switches to Manual Control Level, where manual MV can take priority even during programme RESET. No such key hold or manual control was requested or tested.
  • Simulator patch: Inserted a non-editable a-m page as first MODE after PV/SP, commit 933950f4aa926477a0674e6c9d0be479db304afb, and passed a basic button-flow test. Other Operation Level pages and their visibility have not yet been validated. Simulator’s subsequent r-r screen is provisional, not real-hardware confirmed.
  • Operation-level elapsed time monitor confirmed: While navigating after selecting prg=1, user observed prgt=0 (correcting an earlier transcription of 07). Omron H185 and H177 define prgt as the Elapsed Program Time Monitor; zero is expected before RUN, and is not a programme-selection identifier. pgsg has not yet been rechecked since choosing prg=1. Actual RUN and heater-output behaviour not tested.
  • Operation-level repetition monitor confirmed: On the next Operation Level screen after prgt=0, user observed rptm=0. Omron H177 identifies rptm as Program Execution Repetitions Monitor, different from editable programme rpt. Zero is consistent with no recorded programme repetitions; RUN has not been tested. The pgsg monitor was subsequently observed indicating Programme 1 after selection.
  • RUN/RESET status confirmed: Following prgt=0 → rptm=0, brief MODE displayed r-r=rst in Operation Level. The controller reports RESET, not RUN. This does not verify electrically that the heater/SSR output is inactive. The next display after r-r and the post-selection pgsg value remain to be observed.
  • Physical RUN programme selector and monitor confirmed: After pgsg=0.00, brief MODE displayed prg=0, even though previously edited programme was d.prg=1. User intentionally changed prg from 0 to 1 with mains/heater DC isolated. The user subsequently observed pgsg=1 (as transcribed; exact decimal/segment suffix not yet confirmed). This confirms the monitor changed to Programme 1 even while r-r=rst. After a subsequent complete USB power cycle, user confirmed prg=1 was retained. The RUN/RESET state after this most recent restart was not explicitly reported; no heater RUN or physical output verification has been performed.
  • Power-on RESET indication confirmed on real hardware: After unplugging E58-CIFQ2 USB supply and reconnecting, user verified prg=1 is retained and r-r=rst appears. Combined with p-on=rst surviving an earlier power cycle, this validates the displayed power-on/reset state for USB setup power. It does not verify electrical control output state, restored normal-mains behavior, interrupted RUN recovery, or any independent heater cutoff.
  • Next validation: Optionally record the exact pgsg format on the real controller. The next meaningful stage is a deliberately authorized programme RUN/timing test only after separately checking Omron USB setup power limitations and maintaining verified isolation of all mains and external heater DC supplies. Do not treat a software RESET or an indicated RUN as proof of safe heater output.

13 October 2026 — USB-only programme timer and SV ramp observed

  • Physical PASS — programme execution internally advances with E58-CIFQ2 USB setup power: After setting Operation Level r-r = run (DOWN from rst), the user observed prgt changing over time and the SV (programmed setpoint) increasing. This confirms the real E5CC-T advances its programme clock and calculates an increasing commanded SP while powered from its USB setup cable alone.
  • The user did not observe an on-screen indication of actual heating. That is consistent with no live heater and no controller terminal mains supply; PV response, real output activity, physical heater current, PID following, ramp-to-soak transition, final reset and RUN→RESET key behaviour remain unverified.
  • Manufacturer source: Omron H185 §2-4 states control/alarm/transfer outputs do not operate without the rated controller terminal supply. Its troubleshooting appendix also explicitly states control output cannot turn on when power is supplied via USB-serial conversion cable. H185 §3-3-1 identifies OUT1/OUT2 as assigned control-output indicators on the E5CC-T front; indicator behaviour under USB setup power was not physically checked. The distinct ramp/soak direction status lights pictured for E5EC-T/E5AC-T are not an E5CC-T feature.
  • Important interpretation: A climbing SV is a setpoint command, not an indication of measured heating; the real PV should not be expected to track it on an unheated bench. Output indicator (if active under different powered conditions) is not proof of external 0–60 V heater current.
  • Next physical check: Monitor pgsg at ramp completion if desired, with USB-only and all other supplies isolated. The controller may have wait/hold settings affecting soak entry when PV never reaches SP. Then return to r-r = rst and report the observed button direction and display result before unplugging USB.
  • Sources: https://files.omron.eu/downloads/latest/manual/en/h185_e5_c-t_users_manual_en.pdf (sections 2-4, 3-3-1, Appendix A output troubleshooting).
  • Status: Internal RUN clock/SV ramp PASS; hardware outputs, programme-end action and output-safety functions remain NOT TESTED.
  • Updated code/docs (committed to master): Main manual commit dd3e4e391824413c44b820be2b8357b3e4fa41a2, programming guide commit 75a9378547f1d26c1c728c72efc6e9d17488488d, simulator commit cc0ccb4b7300af8b738a5fe1cfcfee3abe0a1efb. Simulator shows a virtual RST lamp but intentionally does not model OUT1/OUT2 since no actual output observation exists. The +1/+5-minute buttons deliberately accelerate its simulated time while the actual USB-powered unit’s programme clock advances in real time.
  • Regression tests: PASS: JavaScript syntax and tag nesting for all three pages; observed Operation Level order; DOWN from RST → RUN / UP from RST stays RST / expected virtual reverse direction; visual RST status changes; memory power cycle and sample builder. Physical RUN → RESET direction, indicator illumination and soak/end behaviour require new observations.

13 October 2026 — USB-only RUN key behaviour (live physical observation)

  • With the E5CC-T powered only from the E58-CIFQ2 USB setup cable (normal mains and external heater DC isolated), in Operation Level at r-r = rst, the user pressed UP: r-r remained rst. Then the user pressed DOWN: the real display changed to r-r = run.
  • PASS: controller accepts the RUN indication from USB-only setup power. This does not yet show that prgt increments, a segment advances, PV/SP tracks, any output works, or that heater power could energise. Omron’s USB setup-power limitations still apply.
  • Key direction corrected: r-r = rst → DOWN → run. The reverse run → UP → rst is the logical parameter order and now used by the simulator but has not yet been physically validated. Do not assume RESET until it appears on the display.
  • Next physical test: while USB-only, with the controller currently showing r-r = run, use brief MODE presses to locate prgt; record the displayed value and whether it increments. Afterwards verify a deliberate return to r-r = rst before unplugging.
  • Simulator / guide: fixed the RUN/RESET arrow orientation in the virtual keypad and updated the USB-only and normal operating procedures. User must continue maintaining electrical isolation throughout the trial.

13 October 2026 — documentation and simulator consolidation

Next USB-only trial procedure documented: The programming guide now includes USB-only RUN indication check which explicitly requires controller terminal power and heater DC isolated, observes whether r-r=run and prgt change, and returns to rst. H185 also warns against switching the normal controller supply while the USB cable is connected. No physical RUN check yet; this trial cannot verify physical control outputs.

  • Updated user manual: Heating Rate Controller links the validated bench workflow; Omron five-button guide now specifies Programme 1 entry, no separate Save button, full read-back/power-cycle, prg versus d.prg, programme-wide settings, operation monitors, PID-1 observed values, hidden mv-r and USB setup limitations.
  • Updated interactive simulator: Programme Studio includes the real RESET menu sequence (a-m → pgsg → prg → prgt → rptm → r-r), conditional RUN-only monitors, separate editor/RUN selections, browser-persistent virtual programme memory, a virtual power-cycle retaining prg, a one-click load of the verified 50 °C example in Programme 1, and a more complete initial/programme-wide target checklist.
  • Automated simulation tests: PASS: RESET menu order; prg editing and pgsg monitor; virtual power cycle and page-reload memory retention; virtual memory clear; bench example builder row values. Full manual-key test PASS: entered d.prg=1, s-no=2, segment 0 ramp,sp=50,pr=2, segment 1 soak,time=0.15, selected prg=1, simulated power cycle and re-read all values. Tests use a mocked browser DOM and do not exercise real controller outputs.
  • Omron manufacturer limitation — confirmed in H185 §§2-4, 5-23: when powered only from E58-CIFQ2 USB setup cable, the physical unit permits keypad parameter changes and PV display, but control/auxiliary/alarm outputs and event inputs do not operate. It remains unknown whether the actual RUN programme/elapsed timer operates under USB power; no such physical trial completed yet.
  • Outstanding: RUN timing and segment transitions on physical controller, final output commands, physical RESET/output-off verification, protective cut-off and restart inhibition, Channel 2, direct serial connection (Windows E58-CIFQ2 Code 28 still awaiting IT drivers). Confirm exact pgsg decimal segment suffix on the real unit if possible.

Results

  • Actual t-pr: ____ ; actual t-u: ____ ; actual pru: ____
  • Does styp appear for segment 0? ☐ Yes ☐ No
  • Does pr appear when the selected segment is a ramp? ☐ Yes ☐ No
  • Does time appear for a soak? ☐ Yes ☐ No
  • Did short LEVEL/MODE navigation differ from simulator? __________
  • Any unexpected screens or messages: __________
  • Photos recommended: A1–A3, B1–B4, C1–C4, D’s t-pr and rtsm.

Interpretation and next actions

  • Differences in parameter visibility may be caused by the t-pr programming method, active parameter masking, protections, or model/firmware configuration. Record first; do not assume a broken controller.
  • No live-heater, PID response, true temperature tracking, nonvolatile upload/persistence, or safety-interlock behaviour is verified by this menu-only test.
  • Share screenshots or the observations above. Update the simulator from observed controller behaviour and H185 documentation, then repeat this test on Channel 2.
  • Windows Code 28 / no COM port remains an independent IT-driver issue; direct Python communications must wait until Windows exposes the E58-CIFQ2 correctly.

Reference: https://files.omron.eu/downloads/latest/manual/en/h185_e5_c-t_users_manual_en.pdf