Previous documentation — kept for historical comparison. The standard rebuild wiring is now Reference Electrical Wiring R1, including new distribution blocks and all terminal assignments. Do not use this older record as the current rebuild specification. Return to Electrical Overview.
HEATING RATE CONTROLLER / ENGINEERING CHANGE RECORD / 22 OCTOBER 2026

22 October wiring record archive

A practical supplement to the original D12 eleven-sheet schematic set. Applies to the proposed two-channel cabinet and physical wiring reported on 22 October 2026. The original D12 PDF, PowerPoint and image viewer are superseded for the affected terminal and routing details but remain useful as historical schematic references.

ARCHIVED D13 FIELD WORKSHEET — NOT CURRENT WIRING INSTRUCTIONS. Use the R1.2 drawings, connection schedule and terminal distribution for current maintenance references. Manufacturer-verified: Finder 13.61 12–24 V type uses A1/A2 for supply and 3/ON/OFF control, 11/12/14 contacts; Weidmüller 8950770000 uses 13 = high-side output (+) and 14 = low-side output (−); Crydom DR2220D30U uses +3/A1 and −4/A2 for its control input. Reported, not inspected: Crydom +3 shares the EAO pushbutton central contact positive; Crydom −4 and ACTIVE LED− share Weidmüller 13. Still proposed: physical distribution layout, exact terminal stamps, ACTIVE LED+, mains routing, ferrules and final wiring. Power must remain isolated until independently checked.

The 4-page PDF is a condensed printable register (12 mains + 17 CH1 + 17 CH2 individual paths and release holds). The website below includes the more detailed context. Both remain draft engineering documents.

Print on A4 landscape. Individual routes have a blank tick box and an inspection record field. Printed checks do not make this an approved wiring drawing.

WORKSHEET A · MAINS AND PROTECTIVE EARTH

One cabinet, three L take-offs and three N take-offs

The three Live distribution take-offs are PSU, Channel 1 selector input and Channel 2 selector input. The three Neutral distribution take-offs are PSU, E1 and E2. In addition, there are two switched-live wires from the selectors to their Omrons, an incoming L/N feed, and individual protective-earth bonds. The take-off counts are not the complete number of individual conductors.

230 V AC. X1 is a logical distribution name, not an allocated numbered terminal strip. Verify fused/switched inlet poles, selector contact markings, conductor sizing, branch protection, PE continuity and the actual PS1/Omron terminals. Never bridge PE and N or AC neutral and 24 V DC 0 V.

✓Wire / path IDFROMTOPurposeActual terminal / check
□AC-IN-LJ1 switched/fused LX1 Live busIncoming feedProposed; J1 rear terminal mapping unverified
□AC-IN-NJ1 switched NeutralX1 Neutral busIncoming returnProposed; J1 pole mapping unverified
□AC-PS-LX1 Live busPS1 mains L (C1)*1 of 3 L take-offsPhysical PSU designation to be read on label
□AC-S1-LX1 Live busS1 mains NO contact input*2 of 3 L take-offsExact selector contact markings to check
□AC-S2-LX1 Live busS2 mains NO contact input*3 of 3 L take-offsExact selector contact markings to check
□AC-PS-NX1 Neutral busPS1 mains N (C2)*1 of 3 N take-offsPhysical PSU designation to be read on label
□AC-E1-NX1 Neutral busE1 Omron terminal 12 (N)*2 of 3 N take-offsConfirm E1 fitted variant and legend
□AC-E2-NX1 Neutral busE2 Omron terminal 12 (N)*3 of 3 N take-offsConfirm E2 fitted variant and legend
□AC-E1-LS1 mains NO contact output*E1 Omron terminal 11 (L)*Additional switched Live wireThis is NOT another X1 Live take-off
□AC-E2-LS2 mains NO contact output*E2 Omron terminal 11 (L)*Additional switched Live wireThis is NOT another X1 Live take-off
□AC-PE-1J1 PEPE distributionProtective earthingSeparate from N and 24 V 0 V; safety-critical
□AC-PE-2PE distributionPS1 FG/PE, enclosure, door and required bondsMultiple PE conductorsUse individual labelled, tested protective bonds; verify terminals

Cabinet ID __________ Wire tags checked by __________ Independent electrical inspection __________ Date __________

WORKSHEET B · CHANNEL 1 CONTROL (0–24 V)

Channel 1: proposed physical wire connections

There are 3 reported available +24 V distribution positions and 3 reported available 0 V positions per channel. This is a capacity constraint, not a verified terminal-block allocation. Some destinations share junctions. The shared positive at the EAO pushbutton/Crydom and the shared Crydom/ACTIVE negative at Weidmüller 13 were reported by the builder; the specific terminal and both channels have not been inspected.

Status: user-reported cabling ≠ continuity-tested. Verify the EAO central pin really is COM; each double/twin ferrule, jumper and terminal must explicitly support the conductor count and cross-section. Weidmüller PUSH IN terminals are not permission to insert two conductors together. All remaining entries are proposed unless signed off.

✓Wire / path IDFROMTOPurposeActual terminal / check
□C1-DC-01X2 shared +24 VS1 24 V selector B input*Permanent +24 V inContact terminal stamps unknown
□C1-DC-02S1 24 V selector B output* X3 channel +24 V railGated +24 VNot the same as EN1 relay-enabled net
□C1-P1X3 gated +24 VK1 Finder 13.61 A1Switched +24 V destination13.61 L/+ in original D12 was NOT a device terminal
□C1-P2X3 gated +24 VK1 Finder 13.61 11Switched +24 V destinationContact common 11
□C1-P3X3 gated +24 VSB1 EAO momentary COM*Switched +24 V destinationUser describes a central contact pin; physical stamp not yet confirmed
□C1-P4SB1 COM / same verified switched +24 V junctionSSR1 Crydom +3/A1Crydom control positiveUSER-REPORTED shared positive at button contact; verify both channels
□C1-P5X3 gated +24 V / Crydom +3 junctionHL1 ACTIVE indicator +ACTIVE positiveINTENDED connection; installation not confirmed
□C1-N1X3 0 VK1 Finder 13.61 A2Common control 0 V13.61 N/− in D12 was NOT a device terminal
□C1-N2X3 0 VK3 Finder 62.31 coil A2*Common 0 VSocket and suppression mapping unverified
□C1-N3X3 0 VSB1 EAO ENABLE indicator LED−Common 0 VNot the ACTIVE indicator negative
□C1-N4X3 0 VW1 Weidmüller output 14Common 0 VOutput 14 is the low/negative side per manufacturer drawing
□C1-E1SB1 momentary NO*K1 Finder 13.61 terminal 3Pulse commandActual EAO stamp to check
□C1-E2K1 Finder 13.61 output 14K3 Finder 62.31 coil A1*Enabled net EN1Finder 13.61 NO output; socket terminal mapping to verify
□C1-E3K1 Finder 13.61 output 14SB1 ENABLE indicator LED+Enabled net EN1Three-way logical net with K3 A1; junction method unverified
□C1-S1SSR1 Crydom −4/A2W1 Weidmüller output 13SSR switched returnUSER-REPORTED; verify actual W module identification
□C1-S2HL1 ACTIVE indicator −W1 Weidmüller output 13 / SSR1 −4 junctionACTIVE switched returnUSER-REPORTED; confirm both channels and lamp identity
□C1-O1E1 Omron control-output 1(+) / 2(−)*W1 input A1(+) / A2(−)12 V command inputController hardware-dependent outputs must be verified

Channel 1 installer __________ Inspector __________ Test sheet __________ Date __________

WORKSHEET C · CHANNEL 2 CONTROL (0–24 V)

Channel 2: proposed physical wire connections

There are 3 reported available +24 V distribution positions and 3 reported available 0 V positions per channel. This is a capacity constraint, not a verified terminal-block allocation. Some destinations share junctions. The shared positive at the EAO pushbutton/Crydom and the shared Crydom/ACTIVE negative at Weidmüller 13 were reported by the builder; the specific terminal and both channels have not been inspected.

Status: user-reported cabling ≠ continuity-tested. Verify the EAO central pin really is COM; each double/twin ferrule, jumper and terminal must explicitly support the conductor count and cross-section. Weidmüller PUSH IN terminals are not permission to insert two conductors together. All remaining entries are proposed unless signed off.

✓Wire / path IDFROMTOPurposeActual terminal / check
□C2-DC-01X2 shared +24 VS2 24 V selector B input*Permanent +24 V inContact terminal stamps unknown
□C2-DC-02S2 24 V selector B output* X4 channel +24 V railGated +24 VNot the same as EN2 relay-enabled net
□C2-P1X4 gated +24 VK2 Finder 13.61 A1Switched +24 V destination13.61 L/+ in original D12 was NOT a device terminal
□C2-P2X4 gated +24 VK2 Finder 13.61 11Switched +24 V destinationContact common 11
□C2-P3X4 gated +24 VSB2 EAO momentary COM*Switched +24 V destinationUser describes a central contact pin; physical stamp not yet confirmed
□C2-P4SB2 COM / same verified switched +24 V junctionSSR2 Crydom +3/A1Crydom control positiveUSER-REPORTED shared positive at button contact; verify both channels
□C2-P5X4 gated +24 V / Crydom +3 junctionHL2 ACTIVE indicator +ACTIVE positiveINTENDED connection; installation not confirmed
□C2-N1X4 0 VK2 Finder 13.61 A2Common control 0 V13.61 N/− in D12 was NOT a device terminal
□C2-N2X4 0 VK4 Finder 62.31 coil A2*Common 0 VSocket and suppression mapping unverified
□C2-N3X4 0 VSB2 EAO ENABLE indicator LED−Common 0 VNot the ACTIVE indicator negative
□C2-N4X4 0 VW2 Weidmüller output 14Common 0 VOutput 14 is the low/negative side per manufacturer drawing
□C2-E1SB2 momentary NO*K2 Finder 13.61 terminal 3Pulse commandActual EAO stamp to check
□C2-E2K2 Finder 13.61 output 14K4 Finder 62.31 coil A1*Enabled net EN2Finder 13.61 NO output; socket terminal mapping to verify
□C2-E3K2 Finder 13.61 output 14SB2 ENABLE indicator LED+Enabled net EN2Three-way logical net with K4 A1; junction method unverified
□C2-S1SSR2 Crydom −4/A2W2 Weidmüller output 13SSR switched returnUSER-REPORTED; verify actual W module identification
□C2-S2HL2 ACTIVE indicator −W2 Weidmüller output 13 / SSR2 −4 junctionACTIVE switched returnUSER-REPORTED; confirm both channels and lamp identity
□C2-O1E2 Omron control-output 1(+) / 2(−)*W2 input A1(+) / A2(−)12 V command inputController hardware-dependent outputs must be verified

Channel 2 installer __________ Inspector __________ Test sheet __________ Date __________

WORKSHEET D · SUPPLY DISTRIBUTION, JUNCTIONS & RELEASE CHECKS

Distribution counts, actual junction choices and checks

230 V mains distribution — cabinet total

3 X1 Live outgoing positions: PS1 L; S1 mains contact input; S2 mains contact input. 3 X1 Neutral outgoing positions: PS1 N; E1 N; E2 N. Also: J1 incoming L/N, selector outputs to E1/E2 Live, separate PE distribution and bonding.

Whether the installed strips have sufficient physical terminals depends on how the incoming and cross-connected feeds are landed. Count both input and output positions. Never treat N as PE.

24 V distribution — per channel

3 gated +24 V take-off positions and 3 common 0 V take-off positions reported as physically available, not yet inspected.

Illustrative grouping: +1 K1 A1 and 11; +2 SB1 COM and Crydom +3; +3 ACTIVE+; 0V1 K1 A2; 0V2 K3 A2 and ENABLE LED−; 0V3 Weidmüller 14. Alternative approved jumpers are permitted. EN1/EN2 are distinct relay-enabled junctions.

Do not confuse the three positive circuits

+24 shared: always available from PS1 while control supply is on. +24 gated: available after the channel's CONTROL selector. EN1/EN2: only available after Finder 13.61 output 14 closes; supplies K3/K4 A1 and EAO ENABLE LED+.

The ACTIVE lamp is the SSR demand indicator, not actual heater-current proof.

Weidmüller verified topology

Input A1 (+12 V)/A2 (−12 V) is driven by the Omron SSR command. Output transistor terminals 13 (+) and 14 (−) complete the series path +24 gated → Crydom +3 / ACTIVE+ → Crydom −4 / ACTIVE− → W13 → W14 → 0V. Its manufacturer gives 5–48 V DC load, 100 mA maximum; Crydom input up to 15 mA and proposed ACTIVE lamp up to 20 mA (35 mA combined worst-case), subject to actual installed lamp/type and protection.

Connector / ferrule rules

Do not assume two conductors are allowed in one clamp. Check the exact terminal-block maker's permitted conductor count, twin-ferrule dimensions, clamp capacity, strip length and torque. The Weidmüller output is PUSH IN; manufacturer instructions depict two side-by-side inserted wires as incorrect. Use approved distribution junctions where necessary. No X1–X4 numbered terminal assignment has been confirmed.

Mandatory evidence before release

  • Photograph stamped terminals on both Finder 13.61 devices and the EAO contact blocks
  • Verify actual X1–X4 terminal-strip and junction allocation; apply wire markers
  • Dead continuity/insulation and PE bonding test by competent person
  • Verify Weidmüller polarity, SSR demand and LEDs with a safe, low-energy test
  • Prove control-power loss/return cannot re-enable heater, including held pushbutton
  • Verify emergency isolation, protection coordination, 15 A duty and heat dissipation
  • Record as-built, independent review, and revision approval
Legacy schematic correction: old D12 K1/K2 “L/+” and “N/−” = external supply rails, not relay terminals. They map to A1 and A2 only for the confirmed 13.61.0.024.0000 variant. Complete relay code still needs physically checking. This document does not change the D12 PDF/PPTX files themselves.

Inspection checklist signed __________ Drawing issue approved __________ Revision / date __________