Two-channel Heating Rate Controller · Design-review reference

D12 Electrical System · Complete Drawing Viewer

All eleven sheets reproduced directly from the styled editable D12 PowerPoint, without omitting any circuits or connection schedules. Includes explanatory logic and review observations.

DESIGN REVIEW ONLY — NOT APPROVED FOR WIRING OR ENERGISING. Component model differences, restart behaviour, terminal strip hardware, electrical protection and SSR thermal coordination remain open. Use the attached original editable PowerPoint for amendments, not these raster previews.

01 · Mains supply

D12 engineering drawing sheet 1

Use Previous/Next or the number buttons to navigate. Click Zoom to enlarge; scroll within the image to inspect individual terminal connections. These are rendered images of the exact eleven PowerPoint sheets, not a simplified redrawing.

Functional logic — explanatory, not terminal-level wiring

These illustrations explain the D12 interlocks and demand chain. Their roles and terminal numbers come from D12 sheets 1–8; use the original diagrams above for all proposed physical connections.

Shared mains and two separately switched controllers

J1 · 230 V AC

Schurter switched/fused L, N, PE

→
X1 · distribution

Shared AC buses; PE enclosure bonds

→
PS1 · 24 V / 5 A

Mean Well supply stays shared

S1-A

Maintained controller AC contact

→
E1

Omron CH1 temperature controller

S2-A

Maintained controller AC contact

→
E2

Omron CH2 temperature controller

Independent 24 V enable — one per channel

X2 · shared 24 V

Separate from external heater supply

→
S1-B / S2-B

2nd NO selector contact, channel-gated 24 V

→
SB1/SB2 · momentary

Impulse into K1/K2 Finder 13.61

→
K1/K2 · 11→14

Enables K3/K4 62.31 relay coil and switch ring

Key safety assumption, still unverified: power loss/restoration must leave K1/K2 output OFF; normal controller RESET is not sufficient as hardware isolation.

Heater demand and amber activity indication

Type K TC + / −

Green input → Omron 6+/5−

→
E1/E2 · SSR pulse

Omron 1+/2− low-voltage demand

→
W1/W2 · 8950770000

Isolated 12 V-input / DC switching interface

→
SSR input + HL lamp

24 V parallel loads → switched W 13/14 return

The specified yellow ACTIVE lamp (RS 130-1086) draws max 20 mA; the Crydom SSR input draws max 15 mA, for a calculated 35 mA total per channel against the Weidmüller 100 mA DC1 output rating. Verify actual wiring and lamp operation. Neither lamp nor an Omron OUT indicator measures heater current.

External DC heater power — each channel

DC PSU +

External 0–60 V, max 15 A intended

→
QF1/QF2

16 A Lovato DC protective device

→
Finder 62.31

Polarity 34 (+) → 14 (−)

→
Crydom DR2220D30U

Load terminals +1 → −2, controlled SSR

→
Heater +

Outgoing banana jack

Heater − → external PSU −

Separate DC negative return. Finder 14(−) and Crydom −2 remain on the SWITCHED POSITIVE side; neither connects to DC 0 V.

D12 sheet 9 — mains and shared 24 V nets

Original functional net schedule transcribed without allocating physical terminals.

NetSourceDestination
AC01J1 switched fused LX1:L bus
AC02J1 switched NX1:N bus
AC03J1:PEX1:PE + chassis bonds
AC04X1 L / N / PEPS1 C1 / C2 / C3
AC05X1 L → S1-A 13/14E1:11 L
AC06X1 N busE1:12 N
AC07X1 L → S2-A 13/14E2:11 L
AC08X1 N busE2:12 N
DC01PS1 A1 +VoX2 +24 V shared
DC02PS1 A2/A3 −VoX2 0 V shared
DC03X2 +24 → S1-B NOX3 CH1 gated +24
DC04X2 +24 → S2-B NOX4 CH2 gated +24
DC05X2 0 V sharedX3/X4 returns

D12 sheet 10 — both channels

Each line is a functional net description. Refer to sheets 3–8 for terminal/port positions.

TopicConnections as proposed in the uploaded D12
EnableX3/X4 gated +24 to button C and Finder 13.61 L/+ and 11; 0 V to Finder N/−, SK3/4 A2 and EAO LED−.
Momentary inputSB1/2 NO → K1/K2 terminal 3 impulse.
Finder outputK1/K2 NO terminal 14 → SK3/SK4 relay coil A1 and EAO LED+.
ThermocoupleType K + → E1/E2 terminal 6; Type K − → terminal 5.
Omron demandE1/E2 terminals 1 (+), 2 (−) → W1/W2 A1 (+), A2 (−).
SSR and amber pilotGated +24 to SSR input 3+ and HL LED+; SSR 4− and HL LED− to W output 13; W 14 to 0 V.
DC positiveSupply DC+ → QF1/2 terminals 1→2 → Finder 62.31 contact 34 (+)→14 (−) → SSR +1→−2 → heater+.
DC returnHeater− → corresponding external DC PSU−; Finder 14 and SSR −2 are NOT DC−.
Relay coil / socketFinder 62.31 24 V coil uses SK3/SK4 A1/A2, socket family 92.03 suffix TBD; 34/14 contact polarity-sensitive.

Engineering cross-check — open items

Based on the supplied D12 drawing set, the user’s separately recorded physical controller observations and selected manufacturer references. These are discrepancies, missing specifications or release tests, not claims that the circuit has been electrically validated.

Review itemFinding / required validationPriority
Confirm E2 model on nameplateSheet 1 and 6 show E5CC-TQX3A5M-003; the recent two-channel operator documentation has used -000 for both. -003 is a real distinct Omron variant with RS-485 / HB features. Record the actual fitted CH2 type before finalising terminal diagrams.HIGH
Restart inhibition is still unprovenSheets 3–4 and 11 propose Finder 13.61 impulse control and an OFF-after-supply-return state. Verify 13.61 mode and power-loss/recovery behaviour, including held button and short interruption. A programme power-on RESET does not independently break the DC heater supply.HIGH
Check socket suffix and 15 A dutySheets 3–4 and 7–8 use Finder 62.31.9.024.4800 on an unverified 92.03-family socket; confirm A1/A2/34/14 actual terminal mapping and rated continuous current under enclosure temperature.HIGH
Validate selected yellow ACTIVE lamp and 24 V SSR inputHL1/HL2 now specified as RS PRO 130-1086, 24 V DC, 20 mA max, 14 mm cutout, yellow. Crydom input 15 mA max gives 35 mA combined per channel, versus W1/W2 DC1 output max 100 mA. Verify actual fitted lamp, wiring polarity and operation; not a heater-current sensor.MEDIUM
DC breaker/source/thermal coordinationSheets 7–8 show 0–60 V / 15 A per channel, 16 A Lovato breaker, Finder DC relay and Crydom DR2220D30U. Verify available fault current, trip selection, conductor and connector rating, SSR dissipated heat and DC load limits.HIGH
Fix actual terminal and connector namingThe D12 uses JP1-IN/OUT and JP2-IN/OUT for channels 1/2; the interactive operator panel assigns separate JP1/JP2 on CH1 and JP3/JP4 on CH2. These are naming differences; produce one physical identifier list before wiring. X1–X4 net IDs are logical, not ordered hardware terminals.MEDIUM
Validate all protection pathsDD11 inlet fusing/selection, enclosure and door PE continuity, DC supply disconnect/E-stop strategy, sensor-fault MV, SSR-off/reset behaviour and 24 V protective circuits remain for commissioning.HIGH
No proof of heater current from an indicatorACTIVE is an intended control-demand status; rising SV, OUT1 and the amber lamp (if lit) are not measurements of externally delivered DC current. USB-only Omron trials validate programming logic, not heater outputs.MEDIUM

Manufacturer references: Finder series 13 / 62 / 92; Omron E5CC-T -000 versus -003 product data; Weidmüller 8950770000; Crydom DR2220D30U DC SSR. Real control assembly has not been energised for validation.